Siwenoid v2 Minimax configuration

Connecting Mobus RS422 and ATC-1000

Connecting MObus

Modbus RS422 jumpering

RS422

MxSyscon configuration (Modbus configuration, Minimax fire alarm programming interface)

Add and manage modules

XML file

MXGUARD requires an XML file to be imported. This can be extracted from MxSyscon:

- Save program with/without saving to card
- Only in this case will the program temporarily create the XML file in the path described below
- Any program changes have been made, the XML file needs to be updated
- Accessing an XML file on the WIN10 operating system: C:\Users\’username’\Documents\MxSysCon\MxSysCon 5.2\TempProj\’Projekt’\FMZ5000
- Required file from FMZ5000 folder: FMZ5000.XML

ATC UART menu item setting

Mode: RS422
Baudrate: 19200
Character Bits: 8
Parity Type: even
Stop bit: 1
Hardware Flow Control: none

UART Control

Previous → Siwenoid v2 Modbus configuration

Next → Siwenoid v2 Relaydroid configuration