swnd2:bosch_configuration

Bosch FPA5000 configuration

Bosch FPA5000 uses ethernet port to communicate with Siwenoid.

In FSP5000 create an FSI server node under nodes.


(The default Net Node, Group and RSN must be ok) Edit FSI server node's ip properties, this IP Address will be the remote PC's IP. Multicast Address is also neccessary for siwenoid so as Port Number.

nodeedit.jpg


Make sure your FSI server is assigned to every node.

assign_bsch.jpg


The node's (in which the ethernet cable will be plugged in) IP address (CP's IP), Multicast address (same as FSI server), and Port (same as FSI server) are also required to set in. Set the same on control panel.

cpip.jpg


Set the insterted OPC server license for the slot it is plugged in.

opcserver.jpg


Validate every node's FSI server.

validation_1.jpg

Siwenoid's broadcast address is the multicast address that you set here.

Note: This page is based on V1 documentation. A complete V2-specific version is under preparation.

Previous → CerberusPro configuration (SAFEDLINK)